Snow and wind loads

CONTENTS
Snow and wind loads

To calculate buildings and structures, it is necessary to correctly collect the loads in order to correctly select building structures - they must withstand the probable weight, and also not have too much reserve, which will lead to waste of material. Both components are temporary. We will tell you further how to calculate them correctly.

Snow load collection

For the calculation, two components are used - calculated and standard.

Design – load taking into account the safety margin. Adverse conditions are assumed to occur infrequently and are covered by a 40% margin. SP 20.13330.2016 - current standards for calculations, they will be discussed in the article. The coefficient is 1.4. The obtained value is taken into account in the first limit state.

The normative one is the one that preserves operation, while being the maximum. It is needed for the second limit state.

The standard snow load is determined by the formula

1

where c(e) – takes into account the removal of snow cover by the wind, adopted according to paragraphs 10.5-10.9:

  • in the absence of direct wind, in the city – c(e)=1;
  • roofing up to 12%, without protruding parts, with an average wind speed in the 3 coldest months of over 2 m/s:

2

where k – takes into account the change in pressure with height, taken according to table 11.2;

l(c) = 2b-(b*b)/l ≤100 m

where b – width, m;

l – length of the coating, m.

  • roofing 12-20%, without protruding parts - c(e) = 0.85.

A downward marker is not accepted if the average January temperature does not fall below -5 degrees. It does not work when walls and other elements are adjacent.

c(t) – thermal coefficient. In the absence of insulation in the workshop with increased heat generation (over 1 W/(m2C), 3%), c(t)=0.8. In other cases c(t)=1.

Sometimes it is recommended to take it equal to one if the technological process may stop, go on vacation, or be re-equipped. Then the heat generation will stop and the snow will stop melting.

S(g) – standard weight of the cover, calculated in kPa/m2. It is given per squared area at ground level, given in Table 10.1 depends on location (Appendix E, Map 1). Please note that in the new version of the SP the map has been changed.

3

The data is available in the Territorial Building Regulations, and you can also use the map on the website of the Ministry of Construction. Please note: SP is a document that must be followed strictly, TSN is recommendations.

μ – takes into account the transition from a flat horizontal surface on the ground to the complex contours of the roof. It is taken from Appendix B, it depends on the shape of the roof. Interpolation is used to determine intermediate positions.

  • With a slope of up to 12%, it is equal to 1. In the case of a complex roof (a wall higher than the roof, a parapet, a lantern), snow bags form. The calculation is labor-intensive and time-consuming. We will not dwell on it, because... hangars often do not have such elements. If there are any, we will calculate the load correctly and take into account the nuances so that the structure will serve for decades and not pose a threat.
  • A classic awning with a vaulted roof involves the calculation of two coefficients μ.

μ1 = cos (1.5α)

μ2 = sin(3α),

where α is the slope in degrees.

The peculiarity is the calculation at each point, for α ≥60 degrees both coefficients = 0.

  • For a gable roof μ=1 at an angle of up to 30 degrees. μ=0.75 and μ=1.25 – for a slope of 20-30 degrees (different for the two slopes).

4

For 10-30 degrees, take μ=1, μ=0.6 and μ=1.4 at different lengths, choose the most unfavorable option.

If the slope is more than 60 degrees, μ=0.

Wind load collection

Must be taken into account:

  • main wind load;
  • peak;
  • resonant;
  • aerodynamic unstable vibrations.

Resonance and aerodynamics are taken into account if the ratio of the lengths of the longer side to the shorter side exceeds 40 in open areas, 20 when installed against a wall, 10 for buildings where the height is much greater than the width.

The first two are mandatory, for which the reliability coefficient is 1.4. It is needed to obtain the calculated load.

Main wind load:

6

where w(m) is a standard value that depends on the equivalent height z(e):

7

where w(0) is the standard value for the wind region (Appendix E, map 2), according to table 11.1;

8

k(z(e)) – establishes the dependence on altitude characteristics, if h≤300 m, determined according to table 11.2:

z(e) – equivalent height. The parameter d is the width of the wall on which the wind will act, h is the height:

eleven

c – aerodynamic coefficient, depends on the shape of the structure and its section for which the calculation is performed. Section 11.1.7 contains a lot of useful information about each component used for the calculation. You can get the final coefficient by adding the components.

You can talk about each of them for a long time; it’s easier to find Appendix B.1 in the joint venture and take all the necessary coefficients from it.

w(g) – the pulsation component also takes into account the equivalent height that we calculated earlier.

eleven

where w(m) we just calculated;

ζ(z(e)) – pulsation coefficient:

12

v – includes spatial correlation in the calculation. It is accepted according to tables 11.6 and 11.7, everything is described in detail in the SP.

Peak load can be positive and negative (windward and leeward):

13

where w(0), k(z(e)), ζ(z(e)) we defined earlier;

c(p) – peak aerodynamic coefficient of positive pressure and suction, with the corresponding sign. Calculated from previously obtained values, as well as on the basis of Appendix B.1.17.

ν – correlation coefficient for positive pressure and suction for the enclosure area, in m2:

14

Why are loads taken into account in calculations?

In order to correctly select the cross-sectional size of building structures, it is important to understand what load they must bear. To do this, loads are collected:

  • constant - the own weight of the structures themselves;
  • temporary – snow, wind, ice, equipment;
  • special – seismic, explosive, from base deformation.

The data is entered into calculation programs, and they select the most unfavorable combinations, which will allow them to take the maximum load and calculate all the elements for it.

If you do not do this, you may end up with too much supply, which will lead to overexpenditure of materials, funds, and construction time. Especially on the scale of a building and structure, and not a single structure. If you set the cross-section too small, the building or structure will not withstand the pressure of the wind, a layer of snow, or too many people and equipment. This will lead to the destruction of part or the entire structure, and risks will be present during construction and operation.

In addition, without proper documentation, you will not be allowed to start construction, and not a single developer will take up the matter.

In order not to take risks, we suggest turning to professionals for calculations. A person without construction education and experience will not be able to correctly interpret all the points of the regulatory document, and will definitely make a mistake by relying on his intuition. This may lead to unpredictable consequences in the future. After all, having made a mistake at the very beginning of the calculations, you risk calculating everything incorrectly further. That is, all the work will need to be redone, because... no inspection organization will accept it.

Call us, we will do all the calculations, create a project from scratch for any area, and answer all your questions.

Fast installation
(12 to 72 hours)
No capital
foundation required
High mobility
and easy relocation
Easy dismantling
and relocation
Need a consultation?
Our manager will contact you to clarify all details.
Sending...
Previous article

Do you need a prefabricated structure?
Consult us!

×